Series No. 841

Features:

  • 25-30 amps - SPDM or DPDM
  • UL, CSA, and TUV
  • Conforming to VDE 0435
  • 3mm contact gap optional, DPDM
  • .250 Q.C./Solder-lug or PCB terminals
  • AC/DC Coils
  • UPS, air conditioners and heater controller applications

Drawing/Terminal layout:

841.gif

Relay photograph:

Relay 841 Relay 841 Relay 841
DESCRIPTION DETAILS DESCRIPTION DETAILS
Size(LxWxH) not including terminals 51.5X34.9X36 Contact Configuration 1 FORM A TO 2 FORM A
Max.Allowable Contact current 1A - 30 amps, 2A - 25 amps Contact Rating Resistive load 1A - 30A 277VAC
TV-10 125VAC
1 1/2 HP 125VAC
3 HP 277VAC
2A - 25A 277VAC
TV-10 125VAC
1 HP 125VAC
2 HP 277VAC
Insulation System None Coil Voltage DC: 3-200VDC
AC: 6-240VAC
Coil Operating Power at nominal voltage DC: 1.92W
AC: 1.7/2.7VA
Expected mechanical life(min.) 5x10^7
Expected electrical life (min.) 1x10^5 Terminal type General Purpose Relays
Dielectric Strength AC Voltage- 1 minute
Between open contact 2000V Between contact and coil 4000V
Between contact circuits 2000V    
Datasheet
Download this file (841.pdf)841 Relay548 kB